Product Details:
Network Type | 2G |
Compatible Brand | Netgear |
Usage/Application | Industrial |
The BACNET-GW-3 provides an interface between NOTI-FIER’s fire panel network NOTI•FIRE•NETTM (either the stan-dard or the high-speed version) and a network using the
BACnet/IP communication protocol. BACnet protocol is anAmerican National Standard (ANSI/ASHRAE 135-1995). Withthe Gateway interface, devices on NOTI•FIRE•NET fire alarm
control panels are represented as BACnet objects to the BAC-net client. The user subscribes to Event Notification objects
per FACP, and the BACnet device receives events from objectson the FACP as a result of this subscription.The BACNET-GW-3 can be connected to a stand-alone
ONYX® panel with an available network port, or it can be con-nected to NOTI•FIRE•NET via the network port on any net-work control module. Connected to NOTI•FIRE•NET, each
BACNET-GW-3 can support a maximum of 14 other nodes or
15,000 objects. Multiple BACNET-GW-3s can be used to inter-face with larger networks.